Abstract
This paper extends research on single phase microgrids [1] to implement a Virtual Output Impedance (VOI) in a three phase system utilising cascaded PI voltage and current control in the Rotating Reference Frame (RRF). The paper proposes two methods for the selection of VOI values; a selection surface and a summation approach. SABER simulations and dSPACE hardware results are provided for a two inverter microgrid to validate the control scheme and selection techniques.
| Original language | English |
|---|---|
| Title of host publication | 2013 15th European Conference on Power Electronics and Applications, EPE 2013 |
| DOIs | |
| Publication status | Published - 17 Dec 2013 |
| Externally published | Yes |
| Event | 2013 15th European Conference on Power Electronics and Applications, EPE 2013 - Lille, France Duration: 2 Sept 2013 → 6 Sept 2013 |
Conference
| Conference | 2013 15th European Conference on Power Electronics and Applications, EPE 2013 |
|---|---|
| Country/Territory | France |
| City | Lille |
| Period | 2/09/13 → 6/09/13 |
Fingerprint
Dive into the research topics of 'Implementing the virtual output impedance concept in a three phase system utilising cascaded PI controllers in the dq rotating reference frame for microgrid inverter control'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver